1柔性直流输电并网风电厂的低电压穿越能力改进(英文)显示文摘To achieve active control of the AC voltage magnitude of wind power plant(WPP)collector network and improve the fault ride-through(FRT)capability,an FRT scheme based on feed forward DC voltage control is presented for voltage source converter-high voltage direct current(VSC-HVDC)connected offshore WPPs.During steady state operation,an open loop AC voltage control is implemented at the WPP-side VSC of the HVDC system so that any possible control interactions between WPP-side VSC and VSC of wind turbine are minimized.Whereas during any grid fault,a dynamic AC voltage reference is made according to both the DC voltage error and AC active current from the WPP collector system,thus ensuring fast and robust FRT of the VSC-HVDC-connected offshore WPPs.Under the unbalanced fault condition in the host power system,the resulting oscillatory DC voltage is directly used in the VSC AC voltage controller at the WPP side so that the WPP collector system voltage also reflects the unbalance in the main grid.Time domain simulations are performed to verify the efficacy of the FRT scheme based on the proposed feed forward DC voltage control.Simulation results show satisfactory FRT responses of the VSC-HVDC-connected offshore WPP under balanced and unbalanced faults in the host power system,as is shown under a serious fault in the WPP collector network.Ranjan SHARMA Qiuwei WU Seung Tae CHA Kim Hφj JENSEN Tony Wederberg RASMUSSEN Jacob ΦSTERGAARD 2015电力系统自动化2015,39,3:4